Critical Environment Technologies
    Traditional Refrigerants

    R-744

    CO₂

    R-744 (carbon dioxide) is a natural refrigerant used in transcritical and subcritical systems. It has zero ODP and GWP of 1, making it highly environmentally friendly.

    Need R-744 Detection?

    Get expert guidance on the right detection solution for your application.

    Key Information

    Essential safety and exposure information for R-744

    Health Effects

    Concentrations above 3% can cause headaches and dizziness. Above 5% can cause rapid breathing and confusion. Above 10% can cause unconsciousness.

    Common Sources

    • Transcritical supermarket systems
    • industrial refrigeration
    • heat pumps
    • vending machines

    Exposure Limits

    OSHA PEL
    5,000 ppm
    NIOSH REL
    5,000 ppm (ST 30,000)
    ACGIH TLV
    5,000 ppm

    Regulatory Status

    EPA SNAP
    Acceptable substitute
    ASHRAE 34
    A1 Safety Classification
    GWP
    1 (Natural refrigerant)
    ODP
    0
    DOT
    Class 2.2 Non-flammable, UN1013
    Application
    Transcritical systems, cascade

    Detection Requirements

    Sensor Technology
    Infrared (NDIR)
    Detection Range
    0-50,000 ppm (typical for CO₂)
    Response Time
    <30 seconds (T90)
    Cross-Sensitivity
    Minimal for CO₂-specific sensors
    Calibration
    Annual with certified CO₂ standard