Critical Environment Technologies
    Traditional Refrigerants

    R-515B Leak Detectors

    R-1234ze(E)/…

    R-515B (Solstice® N15) is a non-flammable, low-GWP refrigerant developed as a long-term replacement for R-134A in chillers, heat pumps, air conditioning systems, and medium-temperature commercial refrigeration applications. It delivers performance similar to R-134A while reducing GWP by approximately 77-80%.

    Need R-515B Detection?

    Get expert guidance on the right detection solution for your application.

    Key Information

    Essential safety and exposure information for R-515B

    Health Effects

    • ASHRAE safety classification A1 (lower toxicity
    • non-flammable). High vapor concentrations may displace oxygen and create an asphyxiation hazard in poorly ventilated areas.

    Common Sources

    • Centrifugal chillers
    • Screw chillers
    • Heat pumps
    • HVAC systems
    • Medium-temperature commercial refrigeration systems
    • High-ambient air conditioning systems

    Exposure Limits

    WEEL
    1,000 ppm (8-hour TWA) commonly applied to the primary HFO component (R-1234ze(E))
    No specific OSHA PEL established
    No specific OSHA PEL established
    No specific NIOSH REL established
    No specific NIOSH REL established

    Regulatory Status

    EPA SNAP
    Acceptable replacement for R-134a applications
    ASHRAE 34
    A1 Safety Classification
    GWP (AR4)
    292-293
    ODP
    0
    DOT
    Class 2.2 Non-Flammable Gas, UN3163
    F-Gas Status
    Low-GWP refrigerant designed to support regulatory compliance

    Detection Requirements

    Sensor Technology
    Infrared (NDIR)
    Detection Range
    0-2,000 ppm
    Response Time
    <60 seconds (T90)
    Cross-Sensitivity
    Test for blend-specific response
    Calibration
    Annual with target gas recommended