    R-514A (Opteon XP30) is a low-pressure refrigerant for centrifugal chillers. It has B1 classification (higher toxicity, mildly flammable) but ultra-low GWP.

    Need R-514A Detection?

    Get expert guidance on the right detection solution for your application.

    Key Information

    Essential safety and exposure information for R-514A

    Health Effects

    B1 classification indicates higher toxicity than A-class refrigerants. Requires enhanced ventilation and safety measures. Mildly flammable.

    Common Sources

    • Large centrifugal chillers
    • Industrial cooling systems
    • Used as a low-pressure replacement for R-123

    Exposure Limits

    ACGIH TWA 8hr
    200 ppm
    Occupational Exposure Limit (OEL)
    323 ppm (as a total blend)

    Regulatory Status

    EPA SNAP
    Under review
    ASHRAE 34
    B1 Safety Classification
    GWP
    2 (Ultra-low GWP)
    ODP
    0
    DOT
    Class 2.2 Non-flammable
    Application
    Low-pressure chillers

    Detection Requirements

    Sensor Technology
    Infrared (NDIR)
    Detection Range
    0-2,000 ppm
    Alarm Setpoints
    Low 250 ppm, Mid 500 ppm, High 1,000 ppm
    Mounting Height
    Near floor level, near potential leak points, 6–8 inches off floor
    Calibration
    Annual with target gas recommended