CGAS-XP Explosion-Proof Multi-Gas Detector
Reliable, accurate monitoring of toxic or combustible gases in potentially explosive and harsh environments, including hazardous-rated areas.
- Flexible internal and / or remote sensor configurations with up to 3 gas channels
- Field configurable BACnet® MS/TP RS-485 or Modbus® RTU RS-485 digital output signal to controller or BAS
- 1 field selectable 4 - 20 mA output, 0 - 10V or 2 - 10V output, supports VFD control
- Pre-calibrated Plug & Play Smart Sensor replacement at end of life
Description
The cGas-XP Explosion Proof Transmitter is designed to monitor toxic, combustible and refrigerant gases in classified hazardous areas. It can operate as a standalone monitoring device or as part of a larger gas monitoring system.
The unit features three gas channels, three programmable relays, analog output and BACnet® or Modbus® communication for integration with a controller or building automation system.
Sensor configurations support up to two internal sensors, three remote sensors, or one internal and two remote sensors. Its Plug & Play Smart Sensor platform allows quick replacement with pre calibrated sensors. With advanced Smart Sensor technology, the cGas-XP offers sensor life indication, improved system intelligence and a streamlined calibration process for reliable and efficient gas monitoring.
An OLED display with LED indicators provides clear visibility of gas readings, alarm and fault conditions. The intuitive, password protected menu system, combined with enhanced logic control and eight priority/zoning options, allows flexible setup and operation. A security menu allows authorization code entry to lock critical settings.
A magnetic keypad enables full navigation and maintenance access without opening the enclosure. Users can adjust alarm setpoints, modify system configurations and perform non-intrusive calibration with a swipe of the hand.
Specifications
Target Gas
| Electrochemical Sensors | Ammonia (NH3), Carbon monoxide (CO), Hydrogen sulphide (H2S), Nitrogen dioxide (NO2), Oxygen (O2), Sulphur dioxide (SO2) |
| Infrared Sensors | Carbon dioxide (CO2), Butane (C4H10), Ethane (C2H6), Methane (CH4), Propane (C3H8), Refrigerants |
| Catalytic Sensors | Butane (C4H10), Ethanol or Dimethyl Ether (C2H6O), Ethane (C2H6), Ethylene (C2H4), Hexane (C6H14), Hydrogen (H2), Isopropyl Alcohol (C3H8O), Methane (CH4), Methanol (CH4O), Propane (C3H8), Pentane (C5H12), Propylene (C3H6) |
| PID Sensors | TVOC |
Mechanical
| Enclosure | Class 1, Groups A, B, C, D Aluminum pressure die-casting with blue chemically resistant paint |
| Weight | 1 Sensor: 2.2 kg / 4.8 lbs 2 Sensors: 2.17 kg / 2.8 lbs |
| Size | 1 Sensor: 193 x 145 x 128.5 mm / 7.6 x 5.71 x 5.06 in 2 Sensors: 196.5 x 126 x 128.5 mm / 7.7 x 4.96 x 5.06 in |
User Interface
| Display | OLED display 2 x 16 characters with LED panel indicating alarm status 1, 2 and 3 for any channel and FAULT |
| Magnetic Sensors (exterior) | Initiate calibration and menu options with magnetic wand without opening the enclosure; non-intrusive calibration |
| Push Buttons (interior) | Initiate calibration and menu options with push buttons inside the enclosure |
| USB Port | Internal port for USB memory stick for configuration changes and firmware upgrades |
Input/Output
| Input | Up to three 4-20 mA analog inputs |
| Outputs | 1 field selectable 4 - 20 mA output, 0 - 10V or 2 - 10V output, supports VFD control User selectable BACnet® MS/TP (version 1 rev 14) RS-485 or Modbus® RTU (version 1.1b3) RS-485 |
| Relays | 3 SPDT dry contact relays, rated 5A @ 240 VAC |
Electrical
| Power Requirement | 16-30 VDC / 12-28 VAC, 50/60 Hz, 10W |
| Wiring | Low Voltage: 24 VDC or 24 VAC two-conductor shielded 14-18 awg stranded Digital Communication: 4-conductor, 18 - 22 AWG twisted, shielded, stranded within conduit network wiring (daisy-chain) Remote cGas-XP: maximum distance 305 m / 1,000 ft using 3-conductor shielded 14 - 18 awg stranded within conduit |
| Fuses | Thermal, resetting |
Environmental
| Operating Temperature | -40°C to 55°C (-40°F to 131°F) |
| Humidity | 0 - 90% RH non-condensing |
Certifications
| Conforms to | CAN/CSA-C22.2 NO. 61010-1-12, CSA C22.2 NO. 30:20, C22.2 NO. 213-17 UL 61010-1 (3rd Ed.), UL 121201 (9th Ed.), UL 1203 (6 Ed.) Overvoltage Category II, Pollution Degree 2 Hazardous Location Ratings: Class I, Division 1, A, B ,C, D, T4 Class 1, Division 2, A, B ,C, D, T4 Listed by BTL RoHS compliant circuit boards |
Applications
Detected Gases
CGAS-XP Explosion-Proof Multi-Gas Detector Options
13 options available
Showing 1–13 of 13 configurations
CGAS-XP-CO-NO2
CGAS-XP, CO (200ppm) & NO2 (10ppm)
CGAS-XP-CCH4
CGAS-XP, CH4 (100%LEL) (Catalytic)
CGAS-XP-IR410A
CGAS-XP, R410A (2000ppm) (Infrared)
CGAS-XPR-CH2
CGAS-XPR, H2 (100%LEL) (Catalytic)
CGAS-XP-NO2
CGAS-XP, NO2 (10ppm)
CGAS-XP-CCH4-CC3H8
CGAS-XP, CH4 (100%LEL) & C3H8 (100%LEL) (2x Catalytic)
CGAS-XP-CO-O2
CGAS-XP, CO (200ppm) & O2 (25%VOL)
CGAS-XP-CC3H8
CGAS-XP, C3H8 (100%LEL) (Catalytic)
CGAS-XP-O2
CGAS-XP, O2 (25%VOL)
CGAS-XP-CC2H2
CGAS-XP, C2H2 (100%LEL) (Catalytic)
CGAS-XP-CO
CGAS-XP, CO (200ppm)
CGAS-XP-RS
CGAS-XP, Remote Sensor
CGAS-XPR-CH2-100
CGAS-XP, Hydrogen (100%LEL) (Catalytic)
Not all configurations are listed here. Contact our sales team to discuss your specific requirements.
Contact Us