LNK-AO Analog Output Peripheral Device

Adds 4 additional analog outputs to a gas detection system

Adds four channels of 4 - 20 mA analog output to a Modbus® RS-485 network configured with one of the FCS Multi Channel System Controllers.

Applications

  • Parking Facilities
  • Vehicle Repair Shops
  • Manufacturing Plants
  • Food Processing Plants
  • Pools and Arenas
  • and many more...

Key Features

  • Four 4-20 mA output channels
  • Power LED indicator
  • Modbus® RS-485 RTU communication
  • Scaling and zoning capabilities supported by the ontroller
  • Configurable default settings for any interruption in communication
  • Standard water / dust tight, corrosion resistant enclosure

Description

The LNK-AO Analog Output peripheral device adds four channels of 4 - 20 mA analog output to a Modbus® RS-485 network configured with one of the FCS Multi Channel System Controllers. The LNK-AO is designed to send a 4 - 20 mA signal to up to four devices such as a data / trend / logging system, a BAS or DDC or up to four VFDs.

The four 4-20 mA output signals are current sourced and can be independently scaled using the menu system on the controller. Each output can be assigned to an individual sensor or to a group of sensors through zoning configured within the controller. Communication with the controller is monitored and if interrupted a pre-configured default current will be output in each channel.

Mechanical
Enclosure
ABS / Polycarbonate, corrosion resistant
Copper coated interior to reduce RF interference
Weight
400 g / 14 oz
Size
127 x 127 x 71 mm / 5.0 x 5.0 x 2.8 inches
User Interface
Indicator
LED green indicator for power
Input/Output
Output
Four 4-20 m A (2 - 10 volts is obtainable using a 500 Ohm resistor)
Communication
Modbus® RS-485 RTU
Electrical
Power Requirement
24 VDC, 3W, Class 2 (24 VDC supplied by the Controller)
Power Consumption
3 watts
Wiring
4-conductor shielded minimum 18 AWG stranded within conduit
Fuses
Thermal, resetting
Environmental
Operating Temperature
-20°C to 40°C (-4°F to 104°F)
Operating Humidity
15 - 90% RH non-condensing
Certifications
Conforms to:
CSA-C22.2 No. 205-12, UL508 (Edition 17):2007
EMC Directive 2004/108/EC, EN 50270:2006, Type 1, EN61010
FCC. This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
RoHS compliant circuit boards
Product Codes
LNK-AO
Remote Analog Output Peripheral Device, four 4-20 mA outputs, power LED indicator, Modbus® RS-485, water / dust tight, corrosion resistant enclosure