Critical Environment Technologies
    LNK-AO Analog Output Peripheral Device

    LNK-AO Analog Output Peripheral Device

    Adds 4 additional analog outputs to a gas detection system. Adds four channels of 4 - 20 mA analog output to a Modbus® RS-485 network configured with one of the FCS Multi Channel System Controllers.

    • Four 4-20 mA output channels
    • Power LED indicator
    • Modbus® RS-485 RTU communication
    • Scaling and zoning capabilities supported by the controller

    Description

    The LNK-AO Analog Output peripheral device adds four channels of 4 - 20 mA analog output to a Modbus® RS-485 network configured with one of the FCS Multi Channel System Controllers. The LNK-AO is designed to send a 4 - 20 mA signal to up to four devices such as a data / trend / logging system, a BAS or DDC or up to four VFDs.

    The four 4-20 mA output signals are current sourced and can be independently scaled using the menu system on the controller. Each output can be assigned to an individual sensor or to a group of sensors through zoning configured within the controller. Communication with the controller is monitored and if interrupted a pre-configured default current will be output in each channel.

    Specifications

    Mechanical

    EnclosureABS / Polycarbonate, corrosion resistant
    Weight400 g / 14 oz
    Size127 x 127 x 71 mm / 5.0 x 5.0 x 2.8 inches

    User Interface

    IndicatorLED green indicator for power

    Input/Output

    OutputFour 4-20 m A (2 - 10 volts is obtainable using a 500 Ohm resistor)
    CommunicationModbus® RS-485 RTU

    Electrical

    Power Requirement24 VDC, 3W, Class 2 (24 VDC supplied by the Controller)
    Power Consumption3 watts
    WiringVDC supplied by the Controller, 18 - 22 AWG twisted, shielded, stranded within conduit network wiring (daisy-chain)
    FusesThermal, resetting

    Environmental

    Operating Temperature-20°C to 40°C (-4°F to 104°F)
    Operating Humidity15 - 90% RH non-condensing

    Certifications

    Conforms to:CSA-C22.2 No. 205-12, UL508 (Edition 17):2007 EMC Directive 2004/108/EC, EN 50270:2006, Type 1, EN61010 FCC. This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. RoHS compliant circuit boards

    Configure Your LNK-AO Analog Output Peripheral Device

    Select options below to filter configurations.3 configurations available

    Showing 1–3 of 3 configurations

    Product Code
    Qty
    Actions

    LNK-AI

    FCS Network Analog Input

    LNK-AO

    FCS Network Analog Output

    LNK-XT

    FCS Network Modbus extender, RS485

    Not all configurations are listed here. Contact our sales team to discuss your specific requirements.