LNK-AI Analog Input Peripheral Device
Adds 4 additional analog inputs to a gas detection system. The LNK-AI Analog Input peripheral device adds four channels of 4 - 20 mA or 0 - 10 volt analog inputs to a Modbus® network configured with one of the FCS Multi Channel System Controllers.
- Four 4-20 mA input channels
- Power LED indicator
- Modbus® RS-485 RTU communication
- Scaling and zoning capabilities supported by the controller
Description
The LNK-AI Analog Input peripheral device adds four channels of 4 - 20 mA or 0 - 10 volt analog inputs to a Modbus® network configured with one of the FCS Multi Channel System Controllers.
The LNK-AI is designed to receive an analog signal from one to four transmitters and communicates back to the FSC using Modbus® RS-485. The FCS monitors the connection and will indicate a loss of communications. Ideal for large applications to create an efficient distribution network of specialized gas detection devices with fewer wires running directly from the controller.
Specifications
Mechanical
| Enclosure | ABS / Polycarbonate, corrosion resistant |
| Weight | 400 g / 14 oz |
| Size | 127 x 127 x 71 mm / 5.0 x 5.0 x 2.8 inches |
User Interface
| Indicator | LED green indicator for power |
Input/Output
| Input | Four 4-20 mA or 0 - 10 volt analog inputs |
| Communication | Modbus® RS-485 RTU |
Electrical
| Power Requirement | 24 VDC, 1W, Class 2 (24 VDC supplied by the Controller) |
| Power Consumption | 1 watt (not including the devices connected to it) |
| Wiring | VDC supplied by the Controller, 18 - 22 AWG twisted, shielded, stranded within conduit network wiring (daisy-chain) |
| Fuses | Thermal, resetting |
Environmental
| Operating Temperature | -20°C to 40°C (-4°F to 104°F) |
| Operating Humidity | 15 - 90% RH non-condensing |
Certifications
| Conforms to: | CSA-C22.2 No. 205-12, UL508 (Edition 17):2007 EMC Directive 2004/108/EC, EN 50270:2006, Type 1, EN61010 FCC. This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. RoHS compliant circuit boards |
Configure Your LNK-AI Analog Input Peripheral Device
Select options below to filter configurations.3 configurations available
Showing 1–3 of 3 configurations
LNK-AI
FCS Network Analog Input
LNK-AO
FCS Network Analog Output
LNK-XT
FCS Network Modbus extender, RS485
Not all configurations are listed here. Contact our sales team to discuss your specific requirements.
Documents
LNK-AI Datasheet
PDF • 191 KB • Datasheets
LNK-AI Operation Manual
PDF • 621 KB • Manuals
Wiring Diagram: FCS with LNK-AI
PDF • 128 KB • Wiring Diagrams