ASHRAE 15 Refrigerant Detection Requirement Guide
Determine the ASHRAE 15-2024 refrigerant detection requirements for your system. Enter the refrigerant type, system charge, space type, and volume to identify the required OEL trouble-alarm and RCL emergency-alarm setpoints.
Concentration Check
If the entire charge releases: 5.00 lb/1000ft³
RCL for R-32: 4.8 lb/1000ft³
Exceeds RCL — concentration would reach 104% of the RCL. Machinery-room construction and emergency-alarm detection per ASHRAE 15-2024 Section 8.11 are required.
Required Detection Setpoints
Trouble alarm (OEL): ≤ 1,000 ppm
Required in occupied spaces per ASHRAE 15-2024 Section 8.11. Basis: OEL of 1,000 ppm for R-32.
Emergency alarm (RCL): ≤ 30,000 ppm
Required in occupied spaces where the releasable charge exceeds the RCL. Basis: RCL (30,000 ppm), which is lower than 25% LFL.
Advisory Summary
For a 25.0 lb system of R-32 in a 5,000 ft³ occupied space: ASHRAE 15-2024 Section 8.11 applies. A trouble alarm set at or below 1,000 ppm (OEL) plus an emergency alarm at or below 30,000 ppm (RCL) would meet the standard's minimum requirement. Verify against the full standard and your Authority Having Jurisdiction (AHJ).
ASHRAE 34-2022 Refrigerant Safety Data
RCL, LFL, OEL, and GWP values from ANSI/ASHRAE Standard 34-2022 and Addendum a
| Refrigerant | Group | RCL (ppm) | RCL (lb/1000ft³) | LFL (ppm) | OEL (ppm) | GWP |
|---|---|---|---|---|---|---|
| R-32 | A2L | 30,000 | 4.8 | 141,000 | 1,000 | 675 |
| R-454B | A2L | 29,000 | 4.6 | 115,000 | 850 | 466 |
| R-454C | A2L | 29,000 | 4.6 | 77,000 | 620 | 148 |
| R-455A | A2L | 30,000 | 6.8 | 118,000 | 650 | 148 |
| R-1234yf | A2L | 30,000 | 7.6 | 62,000 | 500 | 4 |
| R-1234ze(E) | A2L | 29,000 | 6.9 | 65,000 | 800 | 6 |
| R-717 (Ammonia) | B2L | 320 | 0.014 | 162,000 | 25 | 0 |
| R-744 (CO₂) | A1 | 40,000 | 4.5 | N/A | 5,000 | 1 |
| R-290 (Propane) | A3 | 9,000 | 1.03 | 21,000 | 1,000 | 3 |
| R-410A | A1 | 140,000 | 26 | N/A | 1,000 | 2,088 |
| R-134a | A1 | 60,000 | 13 | N/A | 1,000 | 1,430 |
| R-407C | A1 | 76,000 | 17 | N/A | 1,000 | 1,774 |
| R-404A | A1 | 130,000 | 25 | N/A | 1,000 | 3,922 |
Sources: ANSI/ASHRAE Standards 15-2024 & 34-2022, UL 60335-2-40, IMC 2024 Chapter 11.
Frequently Asked Questions
Related: Refrigeration Monitoring · A2L Transition Guide · Gas Concentration Converter · CET refrigerant detectors
Advisory Disclaimer
This tool is provided for educational and reference purposes only. It summarizes requirements from published standards as of their most recent edition date and does not replace the full text of the applicable standard, local code, or the judgment of a qualified design professional. Values shown here must be verified against the current edition of the relevant standard (ASHRAE 15, ASHRAE 34, IIAR 2, etc.) and the Authority Having Jurisdiction for the project location. Critical Environment Technologies assumes no liability for decisions made using this tool. Always consult a licensed mechanical engineer for system design and compliance determinations.