ASHRAE 15 Refrigerant Detection Requirement Guide
Determine whether ASHRAE 15-2022 requires refrigerant leak detection for your system. Enter the refrigerant type, system charge, space type, and volume to check against the Refrigerant Concentration Limit (RCL) and identify the correct alarm threshold.
Concentration Check
If the entire charge releases: 5.00 lb/1000ft³
RCL for R-32: 4.8 lb/1000ft³
Exceeds RCL — concentration is 104% of the RCL. Detection required per ASHRAE 15-2022 Section 7.5/7.6.
Detection Threshold
Alarm at: 30,000 ppm
Basis: RCL (30,000 ppm), which is lower than 25% LFL
Advisory Summary
For a 25.0 lb system of R-32 in a 5,000 ft³ occupied space: ASHRAE 15-2022 Section 7 applies. A refrigerant detector set to alarm at 30,000 ppm would meet the standard's minimum requirement. Verify against the full standard and your Authority Having Jurisdiction (AHJ).
ASHRAE 15-2022 Detection Requirements
ASHRAE 15-2022 requires refrigerant detection in two scenarios: (1) occupied spaces where the releasable charge could exceed the RCL (Section 7), and (2) machinery rooms with any refrigerant (Section 11). For A2L refrigerants, detectors must alarm at ≤25% of the LFL and trigger:
- Emergency ventilation activation
- Compressor and open-flame equipment shutdown
- Self-test with fault alarm notification
Note: ASHRAE 15-2024 incorporates 14 addenda to the 2022 edition. Verify which edition your local code references.
ASHRAE 34-2022 Refrigerant Safety Data Reference Table
Values from ANSI/ASHRAE Standard 34-2022 and Addendum a
| Refrigerant | Group | RCL (ppm) | RCL (lb/1000ft³) | LFL (ppm) | OEL (ppm) | GWP |
|---|---|---|---|---|---|---|
| R-32 | A2L | 30,000 | 4.8 | 141,000 | 1,000 | 675 |
| R-454B | A2L | 29,000 | 4.6 | 115,000 | 850 | 466 |
| R-454C | A2L | 29,000 | 4.6 | 77,000 | 620 | 148 |
| R-455A | A2L | 30,000 | 6.8 | 118,000 | 650 | 148 |
| R-1234yf | A2L | 30,000 | 7.6 | 62,000 | 500 | 4 |
| R-1234ze(E) | A2L | 29,000 | 6.9 | 65,000 | 800 | 6 |
| R-717 (Ammonia) | B2L | 320 | 0.014 | 162,000 | 25 | 0 |
| R-744 (CO₂) | A1 | 40,000 | 4.5 | N/A | 5,000 | 1 |
| R-290 (Propane) | A3 | 9,000 | 1.03 | 21,000 | 1,000 | 3 |
| R-410A | A1 | 140,000 | 26 | N/A | 1,000 | 2,088 |
| R-134a | A1 | 60,000 | 13 | N/A | 1,000 | 1,430 |
| R-407C | A1 | 76,000 | 17 | N/A | 1,000 | 1,774 |
| R-404A | A1 | 130,000 | 25 | N/A | 1,000 | 3,922 |
Frequently Asked Questions
Related CET Products
FCS Flexible Control System
Multi-channel controller for refrigerant monitoring with BACnet integration and emergency ventilation control.
View Products →cGas Detector
Addressable gas detector with refrigerant sensor options for A2L and conventional refrigerants.
View Products →LPT-A Line Powered Transmitter
Line-powered gas transmitter for machinery room and refrigeration applications.
View Products →See also: Refrigeration Monitoring Applications | Gas Concentration Converter | A2L Refrigerant Transition Guide
Sources & Standards
- ANSI/ASHRAE Standard 15-2022 — Safety Standard for Refrigeration Systems
- ANSI/ASHRAE Standard 34-2022 — Designation and Safety Classification of Refrigerants
- ASHRAE 34-2022 Addendum a (2022) — Updated RCL and LFL values
- UL 60335-2-40, 4th edition — Safety requirements for heat pumps, air conditioners, and dehumidifiers
- International Mechanical Code (IMC) 2024, Chapter 11
Advisory Disclaimer
This tool is provided for educational and reference purposes only. It summarizes requirements from published standards as of their most recent edition date and does not replace the full text of the applicable standard, local code, or the judgment of a qualified design professional. Values shown here must be verified against the current edition of the relevant standard (ASHRAE 15, ASHRAE 34, IIAR 2, etc.) and the Authority Having Jurisdiction for the project location. Critical Environment Technologies assumes no liability for decisions made using this tool. Always consult a licensed mechanical engineer for system design and compliance determinations.