Critical Environment Technologies

    ASHRAE 15 Refrigerant Detection Requirement Guide

    Determine the ASHRAE 15-2024 refrigerant detection requirements for your system. Enter the refrigerant type, system charge, space type, and volume to identify the required OEL trouble-alarm and RCL emergency-alarm setpoints.

    Concentration Check

    If the entire charge releases: 5.00 lb/1000ft³

    RCL for R-32: 4.8 lb/1000ft³

    Exceeds RCL — concentration would reach 104% of the RCL. Machinery-room construction and emergency-alarm detection per ASHRAE 15-2024 Section 8.11 are required.

    Required Detection Setpoints

    Trouble alarm (OEL): ≤ 1,000 ppm

    Required in occupied spaces per ASHRAE 15-2024 Section 8.11. Basis: OEL of 1,000 ppm for R-32.

    Emergency alarm (RCL): ≤ 30,000 ppm

    Required in occupied spaces where the releasable charge exceeds the RCL. Basis: RCL (30,000 ppm), which is lower than 25% LFL.

    Advisory Summary

    For a 25.0 lb system of R-32 in a 5,000 ft³ occupied space: ASHRAE 15-2024 Section 8.11 applies. A trouble alarm set at or below 1,000 ppm (OEL) plus an emergency alarm at or below 30,000 ppm (RCL) would meet the standard's minimum requirement. Verify against the full standard and your Authority Having Jurisdiction (AHJ).

    ASHRAE 15-2024 Detection Requirements

    ASHRAE Standard 15-2024 requires refrigerant detection in occupied spaces and machinery rooms to monitor compliance with occupational exposure limits (OELs) and refrigerant concentration limits (RCLs). In accordance with Section 8.11, one or more refrigerant detectors shall be provided. The detector trouble alarm shall be set to activate at a concentration no greater than the applicable OEL and the emergency alarm shall be set to activate at a concentration no greater than the applicable RCL.

    For A2L refrigerants, the emergency alarm setpoint shall not exceed 25% of the LFL, and the detection system shall trigger:

    • Emergency ventilation activation
    • Compressor and open-flame equipment shutdown
    • Self-test with fault alarm notification
    • An audible and visual alarm inside and outside the entrance to the room

    ASHRAE 34-2022 Refrigerant Safety Data Reference Table

    Values from ANSI/ASHRAE Standard 34-2022 and Addendum a

    RefrigerantGroupRCL (ppm)RCL (lb/1000ft³)LFL (ppm)OEL (ppm)GWP
    R-32A2L30,0004.8141,0001,000675
    R-454BA2L29,0004.6115,000850466
    R-454CA2L29,0004.677,000620148
    R-455AA2L30,0006.8118,000650148
    R-1234yfA2L30,0007.662,0005004
    R-1234ze(E)A2L29,0006.965,0008006
    R-717 (Ammonia)B2L3200.014162,000250
    R-744 (CO₂)A140,0004.5N/A5,0001
    R-290 (Propane)A39,0001.0321,0001,0003
    R-410AA1140,00026N/A1,0002,088
    R-134aA160,00013N/A1,0001,430
    R-407CA176,00017N/A1,0001,774
    R-404AA1130,00025N/A1,0003,922

    Frequently Asked Questions

    Related CET Products

    FCS Flexible Control System

    Multi-channel controller for refrigerant monitoring with BACnet integration and emergency ventilation control.

    View Products →

    cGas Detector

    Addressable gas detector with refrigerant sensor options for A2L and conventional refrigerants.

    View Products →

    See also: Refrigeration Monitoring Applications | Gas Concentration Converter | A2L Refrigerant Transition Guide

    Sources & Standards

    Advisory Disclaimer

    This tool is provided for educational and reference purposes only. It summarizes requirements from published standards as of their most recent edition date and does not replace the full text of the applicable standard, local code, or the judgment of a qualified design professional. Values shown here must be verified against the current edition of the relevant standard (ASHRAE 15, ASHRAE 34, IIAR 2, etc.) and the Authority Having Jurisdiction for the project location. Critical Environment Technologies assumes no liability for decisions made using this tool. Always consult a licensed mechanical engineer for system design and compliance determinations.