DCC-SD Sample Draw System

For monitoring: Ammonia, Carbon monoxide, Ethylene, Ethylene oxide, Formaldehyde, Hydrogen, Hydrogen fluoride, Hydrogen sulphide, Nitric oxide, Sulphur dioxide, Refrigerants, TVOCs

Self-contained, single sensor sample draw gas detection system that draws sample air from locations where it is difficult to install a gas detector

Applications

  • Wastewater Treatment Plants
  • Meat Packing Plants
  • Aerospace Industry
  • Automotive Manufacturing
  • and many more...

Key Features

  • Single sensor
  • 2x16 character LCD display with LED indicators
  • One 5A SPDT dry contact relay
  • One configurable 4- 20 mA output
  • Sample draw pump
  • Adjustable flow meter
  • Blocked flow alarm
  • Standard water / dust tight, corrosion resistant enclosure (drip proof)

Description

The DCC-SD is a self-contained, single sensor, sample draw monitoring system that is designed to draw samples of air from hard to access locations such as shafts, tall ceilings, wells, pits, small rooms and many other locations where it is difficult to install gas detectors. The DCC-SD provides continuous sampling of target air over long periods of time.

The DCC-SD system is designed to be installed outside the target location, at a viewable height, with sample tubing running from the monitoring system to the sampled environment. The sample draw pump pulls air from the area through the tubing, in through the inlet port and over the sensor. The air is then exhausted through the outlet port. If the gas readings are higher than a specified set point, the DCC-SD will go into alarm.

The DCC-SD can be configured with a toxic, combustible or refrigerant sensor and comes with a flow detector, a sample draw pump and an internal adjustable flow meter. Features include one configurable 4 - 20 mA output, one alarm level line voltage relay with field configurable time delays and trigger levels, a blocked flow alarm indicating a dirty filter or clogged tubing and an LCD display with LED indicators for channel alarm status and fault conditions.

The filter should be replaced with it becomes dirty and the tubing should be checked regularly to ensure it remains unblocked. The device has been factory tested with a maximum of 15.24 m / 50 ft of sample tubing. For the best response, the sample tubing between the sample point and the inlet port should be kept as short as possible.

Caution: The DCC-SD sample draw system should not be used inside classified hazardous areas or to sample draw combustible gases because the pump is not intrinsically safe. 

Target Gas
Gas Sensors
Ammonia (NH3), Carbon Monoxide (CO), Ethylene (C2H4), Ethylene Oxide (C2H4O), Formaldehyde (CH2O), Hydrogen (H2), Hydrogen Fluoride (HF), Hydrogen Sulphide (H2S), Nitric Oxide (NO), Oxygen (O2), Sulphur Dioxide, (SO2), R22, R134A, R402A, R404A, R407C, R410A, R422D, R438A, R507A, TVOCs
Mechanical
Enclosure
Water / dust tight corrosion resistant polyester reinforced fiberglass
Weight
3.4 kg / 7.5 lbs
Size
223 x 267 x 159 mm / 8.8 x 10.5 x 6.3 inches
Tygon Polymer Tubing (sold separately)
1/8" ID x 1/4" OD, clear, 15.24 m / 50 ft roll sold separately (p/n: CET-8000-CMT)
Teflon Lined Tubing (sold separately)
For use with DCC-SD-NH3, special non-absorbent, 13/16" ID x 5/16" OD, clear, 15.24 m / 50 ft roll sold separately (p/n: CET-8000-CTRL)
User Interface
Display
2x16 character LCD display
LED indicators for "CH1" state, "CH2" state and "FAULT"
SILENCE Push Button
Temporarily clears buzzer / latched relays
Input/Output
Output
One 4-20 mA analog
Relay
One SPDT dry contact relay rated 5 amps @ 240 VAC
Blocked Flow Alarm
Side mounted buzzer, rated 90 dB @ 30 cm / 1 ft
Flow
Normal operation: 1.0 LPM
Flow alarm: less than 0.5 LPM
Electrical
Power Requirement
24 VAC nominal, 10 W, Class 2
Current Draw
400 mA RMS @ 24 VAC
Wiring
24 VAC 2-conductor shielded minimum 18 AWG stranded within conduit
Fuses
Thermal, resetting
Environmental
Operating Temperature
-20°C to 40°C (-4°F to 104°F)
Operating Humidity
15 - 90% RH non-condensing
Location
Indoor use only. Not for use in classified hazardous areas or to sample draw combustible gases.
Certifications
Conforms to
CSA-C22.2 No. 205-12, UL508 (Edition 17):2007
EMC Directive 2004/108/EC, EN 50270:2006, Type 1, EN61010
FCC. This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
RoHS compliant circuit boards
Product Codes
DCC-SD-NH3
Electrochemical ammonia (NH3) sensor (0 - 500 PPM range), LCD display with LED indicators, loud audible alarm, sample draw pump, flow detector with blocked flow alarm, internal adjustable flow meter, one 5A @ 240 VAC SPDT relays, one configurable 4-20 mA output, 24 VAC, water / dust tight enclosure, requires special non-absorbent Teflon lined tubing (sold separately)
DCC-SD-COA
Electrochemical 3-year carbon monoxide (CO) sensor (0 - 200 PPM range), LCD display with LED indicators, loud audible alarm, sample draw pump, flow detector with blocked flow alarm, internal adjustable flow meter, one 5A @ 240 VAC SPDT relays, one configurable 4-20 mA output, 24 VAC, water / dust tight enclosure, requires standard Tygon polymer tubing (sold separately)
DCC-SD-C2H4
Electrochemical ethylene (C2H4) sensor (0 - 200 PPM range), LCD display with LED indicators, loud audible alarm, sample draw pump, flow detector with blocked flow alarm, internal adjustable flow meter, one 5A @ 240 VAC SPDT relays, one configurable 4-20 mA output, 24 VAC, water / dust tight enclosure, requires standard Tygon polymer tubing (sold separately)
DCC-SD-EETO
Electrochemical ethylene oxide (C2H4O) sensor (0 - 20 PPM range), LCD display with LED indicators, loud audible alarm, sample draw pump, flow detector with blocked flow alarm, internal adjustable flow meter, one 5A @ 240 VAC SPDT relays, one configurable 4-20 mA output, 24 VAC, water / dust tight enclosure, requires standard Tygon polymer tubing (sold separately)
DCC-SD-CH2O
Electrochemical formaldehyde (CH2O) sensor (0 - 5 PPM range), LCD display with LED indicators, loud audible alarm, sample draw pump, flow detector with blocked flow alarm, internal adjustable flow meter, one 5A @ 240 VAC SPDT relays, one configurable 4-20 mA output, 24 VAC, water / dust tight enclosure, requires standard Tygon polymer tubing (sold separately)
DCC-SD-EH2
Electrochemical hydrogen (H2) sensor (0 - 2,000 PPM range), LCD display with LED indicators, loud audible alarm, sample draw pump, flow detector with blocked flow alarm, internal adjustable flow meter, one 5A @ 240 VAC SPDT relays, one configurable 4-20 mA output, 24 VAC, water / dust tight enclosure, requires standard Tygon polymer tubing (sold separately)
DCC-SD-HF
Electrochemical hydrogen fluoride (HF) sensor (0 - 10 PPM range), LCD display with LED indicators, loud audible alarm, sample draw pump, flow detector with blocked flow alarm, internal adjustable flow meter, one 5A @ 240 VAC SPDT relays, one configurable 4-20 mA output, 24 VAC, water / dust tight enclosure, requires standard Tygon polymer tubing (sold separately)
DCC-SD-H2S
Electrochemical 2+ years hydrogen sulphide (H2S) sensor (0 - 50 PPM range), LCD display with LED indicators, loud audible alarm, sample draw pump, flow detector with blocked flow alarm, internal adjustable flow meter, one 5A @ 240 VAC SPDT relays, one configurable 4-20 mA output, 24 VAC, water / dust tight enclosure, requires standard Tygon polymer tubing (sold separately)
DCC-SD-H2SB
Electrochemical 5+ years hydrogen sulphide (H2S) sensor (0 - 50 PPM range), LCD display with LED indicators, loud audible alarm, sample draw pump, flow detector with blocked flow alarm, internal adjustable flow meter, one 5A @ 240 VAC SPDT relays, one configurable 4-20 mA output, 24 VAC, water / dust tight enclosure, requires standard Tygon polymer tubing (sold separately)
DCC-SD-NO
Electrochemical nitric oxide (NO) sensor (0 - 100 PPM range), LCD display with LED indicators, loud audible alarm, sample draw pump, flow detector with blocked flow alarm, internal adjustable flow meter, one 5A @ 240 VAC SPDT relays, one configurable 4-20 mA output, 24 VAC, water / dust tight enclosure, requires standard Tygon polymer tubing (sold separately)
DCC-SD-SO2
Electrochemical sulphur dioxide (SO2) sensor (0 - 20 PPM range), LCD display with LED indicators, loud audible alarm, sample draw pump, flow detector with blocked flow alarm, internal adjustable flow meter, one 5A @ 240 VAC SPDT relays, one configurable 4-20 mA output, 24 VAC, water / dust tight enclosure, requires standard Tygon polymer tubing (sold separately)
DCC-SD-SR22
Solid state refrigerant (R22) sensor (0 - 2,000 PPM range), LCD display with LED indicators, loud audible alarm, sample draw pump, flow detector with blocked flow alarm, internal adjustable flow meter, one 5A @ 240 VAC SPDT relays, one configurable 4-20 mA output, 24 VAC, water / dust tight enclosure, requires standard Tygon polymer tubing (sold separately)
DCC-SD-SR134A
Solid state refrigerant (R134A) sensor (0 - 2,000 PPM range), LCD display with LED indicators, loud audible alarm, sample draw pump, flow detector with blocked flow alarm, internal adjustable flow meter, one 5A @ 240 VAC SPDT relays, one configurable 4-20 mA output, 24 VAC, water / dust tight enclosure, requires standard Tygon polymer tubing (sold separately)
DCC-SD-SR402A
Solid state refrigerant (R402A) sensor (0 - 2,000 PPM range), LCD display with LED indicators, loud audible alarm, sample draw pump, flow detector with blocked flow alarm, internal adjustable flow meter, one 5A @ 240 VAC SPDT relays, one configurable 4-20 mA output, 24 VAC, water / dust tight enclosure, requires standard Tygon polymer tubing (sold separately)
DCC-SD-SR404A
Solid state refrigerant (R404A) sensor (0 - 2,000 PPM range), LCD display with LED indicators, loud audible alarm, sample draw pump, flow detector with blocked flow alarm, internal adjustable flow meter, one 5A @ 240 VAC SPDT relays, one configurable 4-20 mA output, 24 VAC, water / dust tight enclosure, requires standard Tygon polymer tubing (sold separately)
DCC-SD-SR407C
Solid state refrigerant (R407) sensor (0 - 2,000 PPM range), LCD display with LED indicators, loud audible alarm, sample draw pump, flow detector with blocked flow alarm, internal adjustable flow meter, one 5A @ 240 VAC SPDT relays, one configurable 4-20 mA output, 24 VAC, water / dust tight enclosure, requires standard Tygon polymer tubing (sold separately)
DCC-SD-SR410A
Solid state refrigerant (R410A) sensor (0 - 2,000 PPM range), LCD display with LED indicators, loud audible alarm, sample draw pump, flow detector with blocked flow alarm, internal adjustable flow meter, one 5A @ 240 VAC SPDT relays, one configurable 4-20 mA output, 24 VAC, water / dust tight enclosure, requires standard Tygon polymer tubing (sold separately)
DCC-SD-SR422D
Solid state refrigerant (R422D) sensor (0 - 2,000 PPM range), LCD display with LED indicators, loud audible alarm, sample draw pump, flow detector with blocked flow alarm, internal adjustable flow meter, one 5A @ 240 VAC SPDT relays, one configurable 4-20 mA output, 24 VAC, water / dust tight enclosure,requires standard Tygon polymer tubing (sold separately)
DCC-SD-SR438A
Solid state refrigerant (R438A) sensor (0 - 2,000 PPM range), LCD display with LED indicators, loud audible alarm, sample draw pump, flow detector with blocked flow alarm, internal adjustable flow meter, one 5A @ 240 VAC SPDT relays, one configurable 4-20 mA output, 24 VAC, water / dust tight enclosure, requires standard Tygon polymer tubing (sold separately)
DCC-SD-SR507A
Solid state refrigerant (R507A) sensor (0 - 2,000 PPM range), LCD display with LED indicators, loud audible alarm, sample draw pump, flow detector with blocked flow alarm, internal adjustable flow meter, one 5A @ 240 VAC SPDT relays, one configurable 4-20 mA output, 24 VAC, water / dust tight enclosure, requires standard Tygon polymer tubing (sold separately)
DCC-SD-STVOC
Solid state TVOC sensor (0 - 500 PPM range), LCD display with LED indicators, loud audible alarm, sample draw pump, flow detector with blocked flow alarm, internal adjustable flow meter, one 5A @ 240 VAC SPDT relays, one configurable 4-20 mA output, 24 VAC, water / dust tight enclosure, requires standard Tygon polymer tubing (sold separately)
CET-8000-CMT
Standard Tygon polymer clear sample draw tubing, 1/8" ID x 1/4" OD, 15.24 m / 50 ft roll sold separately
CET-8000-CTRL
For use with DCC-SD-NH3, Teflon lined, special non-absorbent sample draw tubing, 13/16" ID x 5/16" OD, 5.24 m / 50 ft roll sold separately

Options, Accessories and More...