cGas Detector Ammonia Vent Line Transmitter

For continuous monitoring of Ammonia levels in the vent line of refrigeration systems

Mount indoors on the ammonia vent relief stack in refrigeration systems to help detect equipment failure

Applications

  • Ice Arenas
  • Refrigeration Plants
  • Cold Storage Rooms
  • Freezer Rooms
  • Ammonia Plants
  • and many more...

Key Features

  • Single channel, internal catalytic Ammonia sensor
  • 4-20 mA analog output or user configurable in the field, BACnet® MS/TP (version 1 rev 14) RS-485 or Modbus® RTU (version 1.1b3) RS-485
  • 24 VDC or VAC power (ground referenced)
  • Easy Plug & Play Smart Sensor replacement at end of life, comes pre-calibrated
  • Bright LCD display
  • USB port for configuration changes and firmware upgrades
  • Optional 2A SPDT dry contact relay (Option -RLY)
  • Optional low temperature operation package (Option -LT)
  • Standard water / dust tight, corrosion resistant enclosure (drip proof)
  • Thermal resetting fuses
  • RoHS compliant circuit board

Description

The cGas Ammonia Vent Line Detector is designed for continuous monitoring of ammonia levels in the vent line of refrigeration systems, including the detection of equipment failure in ammonia plant vent stack applications. Using a a ¾” cast steel coupler, the cGas Ammonia Vent Line Detector is to be mounted indoors on the ammonia vent relief stack above the pressure relief valve.

With the optional relay, it can be configured to send an analog signal to the controller or PLC to activate the emergency ventilation system or shut down the equipment depending on the level of alarm.

Powered by 24 VDC or ground referenced AC, the CGAS Detector has an LCD display and the firmware and configuration can be upgraded in the field using the USB connection. The Plug & Play Smart Sensor comes pre-calibrated and is easy to replace.

It comes standard with a water / dust tight, corrosion resistant ABS / polycarbonate enclosure with a hinged, secured door.  A factory installed splash guard protects the device against water ingress.

NOTE: This device is not designed to monitor ammonia in applications requiring human health safety levels detection. The lowest reading the sensor will detect is above the recommended exposure limit to ammonia. A large release of a high concentration of ammonia may burn out the sensor and it will require replacement.

Target Gas
Gas Sensor
Ammonia (NH3), measurement range 0 - 3.00% volume
Tolerant to 17% volume. NOTE: Ammonia is flammable between 15% (LEL) and 28% (UEL) volume in air.
Sensor
Type
Catalytic
Response Time T90
30 seconds
Mechanical
Enclosure
Black ABS / Polycarbonate, copper coated interior to reduce RF interference
IP54 rated with splash guard installed
Weight
825 g / 29 oz
Size
Detector with splash guard: 127 x 127 x 84 mm / 5.0 x 5.0 x 3.3 in
Completely assembled product: 127 x 127 x 182.5 mm / 5.0 x 5.0 x 7.18 in
Coupler
19.5 mm / 3/4 inch NPT, cast steel
Sensor Assembly Length (including coupler)
98.5 mm / 3.875 inches
User Interface
Display (Standard)
2-line by 16 character graphic LCD
Operating Temperature: 0°C to 40°C / 32°F to 104°F
Display (Option -LT)
2-line by 16 character OLED display and internal heater
Operating Temperature: -40°C to 40°C / -40°F to 104°F
Push Buttons
Initiate calibration and menu options with internal UP, DOWN and ENTER push buttons
USB Port
Internal port for USB memory stick for field configuration updated / firmware upgrades
Input/Output
Analog (CGAS-A-VLT model)
Linear 4 - 20 mA analog
Maximum 216 ohm load (wiring plus termination resistor) @ 12 VDC
Maximum 316 ohm load (wiring plus termination resistor) @ 12 VAC
Digital (CGAS-D-VLT Model)
User configurable in the field, BACnet® MS/TP (version 1 rev 14) RS-485 or Modbus® RTU (version 1.1b3) RS-485
Relay (Option -RLY)
1 SPDT dry contact relay, rated 30 volts @ 2 amps
Electrical
Power Requirement
3-wire: 16-30 VDC, 3W, Class 2
4-wire: 12-27 VAC, 50-60 Hz, 3 VA, Class 2
24V recommended
Wiring (CGAS-A-VLT model)
VDC (or ground referenced AC): 3-conductor 18 AWG (or larger) shielded, stranded within conduit
VAC 4-conductor shielded 18 AWG stranded within conduit
Wiring (CGAS-D-VLT Model)
VDC or VAC (ground referenced) 4-conductor shielded 16 AWG stranded within conduit, network wiring (daisy-chain)
Fuses
Automatic resetting thermal
Environmental
Operating Temperature
0°C to 40°C (32°F to 104°F), temperatures below 0°C / 32°F require Option-LT
Operating Humidity
15 - 80% RH non-condensing
Certifications
Conforms to
CSA-C22.2 No. 205-12, UL508 (Edition 18):2018
EMC Directive 2014/30/EU, EN 50270:2015, Type 1, EN61010
FCC. This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
RoHS compliant circuit boards
Product Codes
CGAS-A-VLT-NH3-S
Catalytic ammonia (NH3) sensor (0 - 3.00% volume range), LCD display, one analog 4-20 mA output, Plug & Play Smart sensor replacement, water / dust tight enclosure rated IP54 with splash guard; power coated cast steel sensor assembly and coupler for mounting on ammonia vent relief stack
CGAS-D-VLT-NH3-S
Catalytic ammonia (NH3) sensor (0 - 3.00% volume range), LCD display, field configurable Modbus® RTU RS-485 or BACnet® MS/TP output, Plug & Play Smart sensor replacement, water / dust tight enclosure rated IP54 with splash guard; power coated cast steel sensor assembly and coupler for mounting on ammonia vent relief stack
Factory Options
-LT
Low temperature package with OLED display and internal heater for cold environment applications down to -40°C / -40°F
-RLY
1 SPDT dry contact relay, rated 30 volts, 2 amps max

Options, Accessories and More...