SCC Self Contained Controller

2 channel dependable self-contained Controller with flexible internal and/or remote sensor configurations

Features LED indicators and one configurable 4-20 mA input; for monitoring: Carbon monoxide, Nitrogen dioxide, Hydrogen, Methane, Propane

Applications

  • Parking Facilities
  • Vehicle Repair Shops
  • Battery Charging Rooms
  • Buildings on Landfill Sites
  • and many more...

Key Features

  • Single or dual channel operation
  • Flexible internal and/or remote sensor configurations
  • LED indicators for Power, Ch1, CH2 and Fault
  • Two dry contact relays, 5-amps @240 volts each
  • One configurable 4-20 mA input
  • Line Voltage (90-240 VAC) or Low Voltage (24 VAC/VDC)
  • Internal audible alarm
  • Standard water / dust tight, corrosion resistant enclosure (drip proof); IP54 rated with water tight, door mounted audible alarm installed

Description

The SCC Self Contained Controller is available in one or two channel configurations for monitoring toxic and/or combustible gas types by means of an internal electrochemical Carbon monoxide (CO) or Nitrogen dioxide (NO2) sensor and one of three ESH-A remote catalytic combustible sensors used to detect Hydrogen (H2), Propane (C3H8) or Methane (CH4). Monitoring of CO or NO2 may also be achieved remotely by combining the SCC with a 4-20 mA transmitter such as the LPT-TCO or LPT-END.

The SCC also features two alarm level line voltage relays with field configurable time delays and trigger levels, a field selectable internal audible alarm and an LED panel indicating power, channel alarm status and fault conditions.

Automated calibration and other maintenance procedures are simple and easily performed in the field, and our proprietary Calibration Extending Firmware (CEF) takes into account the aging of the toxic gas sensors so that less frequent calibrations are required in less-critical applications such as parking garages.

Target Gas
Gas Sensors
Carbon Monoxide (CO), Nitrogen Dioxide (NO2), Hydrogen (H2), Methane (CH4), Propane (C3H8)
Mechanical
Enclosure
ABS / Polycarbonate, corrosion resistant
Copper coated interior to reduce RF interference
IP54 rated with optional splash guard installed
Weight
1.18 kg / 2.6 lbs
Size
254 x 226 x 113 mm / 10.0 x 8.9 x 4.44 inches
User Interface
Display
LED indicators for “CH1" state, "CH2" state and “FAULT”
Input/Output
Input
4-20 mA analog
Output
none
Relay
Two internal SPDT dry contact relays rated 5 amps @ 240 VAC
Audible Alarm
Standard internal buzzer, rated 76 dB @ 3 m (10 ft)
Electrical
Power Requirement
Low Voltage: 16-30 VDC or 12-30 VAC, 10 W Class 2
Line Voltage: 90 – 240 VAC, 50 -60 Hz
Wiring
Low Voltage: 24 VDC or 24 VAC 2-conductor shielded minimum 18 AWG stranded within conduit
Line Voltage: VAC 3-conductor shielded minimum 18 AWG stranded within conduit
Distance
Maximum 61 m / 200 ft between controller and ESH-A Remote Sensor using minimum 18 AWG stranded within conduit
Fuses
Thermal, resetting
Environmental
Operating Temperature
-20°C to 40°C (-4°F to 104°F)
with internal heater
-40°C to 40°C (-40°F to 104°F)
Operating Humidity
15 - 90% RH non-condensing
Certifications
Conforms to:
CSA-C22.2 No. 205-M1983 (R2009), UL508 (Edition 17):2007
EMC Directive 2004/108/EC, EN 50270:2006, Type 1, EN61010
FCC. This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
RoHS compliant circuit boards
Product Codes
SCC-A-TCO
Single channel, internal electrochemical 6-year carbon monoxide (CO) sensor (0 - 200 ppm range), LED indicators, two 5A @ 240 VAC SPDT relays, audible alarm, low voltage 16 – 30 VDC or 12 – 28 VAC, 10W, Class 2, line voltage 90 – 240 VAC, 50 – 60 Hz, water / dust tight enclosure 
SCC-A-NO2B
Single channel, internal electrochemical 6-year nitrogen dioxide (NO2) sensor (0 - 10 ppm range), LED indicators, two 5A @ 240 VAC SPDT relays, audible alarm, low voltage 16 – 30 VDC or 12 – 28 VAC, 10W, Class 2, line voltage 90 – 240 VAC, 50 – 60 Hz, water / dust tight enclosure
SCC-B-R
Single channel, no internal sensor (set up to accept ESH-A remote sensor), LED indicators, two 5A @ 240 VAC SPDT relays, audible alarm, low voltage 16 – 30 VDC or 12 – 28 VAC, 10W, Class 2, line voltage 90 – 240 VAC, 50 – 60 Hz, water / dust tight enclosure 
SCC-B-RT
Single channel, no internal sensor, must add remote 4-20 mA transmitter, includes LED indicators, two 5A @ 240 VAC SPDT relays, audible alarm, low voltage 16 – 30 VDC or 12 – 28 VAC, 10W, Class 2, line voltage 90 – 240 VAC, 50 – 60 Hz, water / dust tight enclosure
SCC-D-TCO-R
Dual channel, internal electrochemical 6-year carbon monoxide (CO) sensor (0 - 200 ppm range), must add ESH-A remote sensor, LCD display with LED indicators, two 5A @ 240 VAC SPDT relays, two 4-20 mA outputs, audible alarm, low voltage 16 – 30 VDC or 12 – 28 VAC, 10W, Class 2, line voltage 90 – 240 VAC, 50 – 60 Hz, water / dust tight enclosure  
SCC-D-TCO-RT
Dual channel, internal electrochemical 6-year carbon monoxide (CO) sensor (0 - 200 ppm range), must add remote 4-20 mA transmitter, LCD display with LED indicators, two 5A @ 240 VAC SPDT relays, two 4-20 mA outputs, audible alarm, low voltage 16 – 30 VDC or 12 – 28 VAC, 10W, Class 2, line voltage 90 – 240 VAC, 50 – 60 Hz, water / dust tight enclosure  
SCC-D-NO2B-R
Dual channel, internal electrochemical carbon monoxide (CO) sensor (0 - 200 ppm range), must add ESH-A remote sensor, LED indicators, two 5A @ 240 VAC SPDT relays, audible alarm, low voltage 16 – 30 VDC or 12 – 28 VAC, 10W, Class 2, line voltage 90 – 240 VAC, 50 – 60 Hz, water / dust tight enclosure  
SCC-D-NO2B-RT
Dual channel, internal electrochemical nitrogen dioxide (NO2) sensor (0 - 10 ppm range), must add a remote LPT-TCO Transmitter with internal electrochemical carbon monoxide (CO) sensor (0 -200 ppm range), includes LED indicators, two 5A @ 240 VAC SPDT relays, audible alarm, low voltage 16 – 30 VDC or 12 – 28 VAC, 10W, Class 2, line voltage 90 – 240 VAC, 50 – 60 Hz, water / dust tight enclosure
SCC-E-TCO-NO2B
Dual channel, internal electrochemical carbon monoxide (CO) sensor (0 - 200 ppm range) plus internal electrochemical nitrogen dioxide (NO2) sensor (0 - 10 ppm range), LED indicators, two 5A @ 240 VAC SPDT relays, audible alarm, low voltage 16 – 30 VDC or 12 – 28 VAC, 10W, Class 2, line voltage 90 – 240 VAC, 50 – 60 Hz, water / dust tight enclosure 
Factory Options
-IH
Internal heater for cold environment applications down to -40°C / 40°F
-S
Splash Guard, factory installed, IP54 rating
Remote Sensors
ESH-A-CH2-100
Catalytic Hydrogen (H2) ESH Remote Sensor (0 - 100% LEL), water / dust tight enclosure 
ESH-A-CCH4-100
Catalytic Methane (CH4) ESH Remote Sensor (0 - 100% LEL), water / dust tight enclosure 
ESH-A-CC3H8-100
Catalytic Propane (C3H8) ESH Remote Sensor (0 - 100% LEL), water / dust tight enclosure 
Compatible Analog (4-20 mA) Transmitters
LPT-END
Single channel analog gas detector with internal electrochemical NO2 sensor (0 - 10 ppm range)
LPT-TCO
Single channel analog gas detector with internal electrochemical CO sensor (0 - 200 ppm range)

Options, Accessories and More...