Sensor Mounting Heights & Location
The sensor mounting height depends on the density of the gas relative to air. Heavier than air gases should be detected 6 inches from the floor, lighter than air gas sensors should be placed on or near the ceiling, and gases which have a density close to that of air should have sensors installed in the "breathing zone" 4 to 6 feet from the floor. The breathing zone refers to the area 4 to 6 feet from the floor, where most human breathing takes place. This is a good default location for sensors, as many gases are often well dispersed in air.
Consideration should be given to accessibility for calibration when locating sensors. For example, a sensor mounted 30 feet off the floor will be difficult or even hazardous to service.
Sensors should be placed near the source of the gas if possible. For example, near the compressor or piping.
Sensors should not be placed near ventilation fans or openings to outside. They should be placed in areas where there is good air circulation, but not in the path of rapidly moving air. Pay particular attention to "dead air spots" where there is little or no air movement.
Mounting Heights for Common Gases:
| CO | Carbon Monoxide |
| CO2 | Carbon Dioxide |
| O2 | Oxygen |
| NO | Nitric Oxide |
| NO2 | Nitrogen Dioxide |
| H2S | Hydrogen Sulphide |
| CO2 | Carbon Dioxide (Industrial or Beverage applications) |
| Cl2 | Chlorine |
| O3 | Ozone |
| C3H8 | Propane |
| Refrigerants (Freons) |
| NH3 | Ammonia |
| CH4 | Methane (Natural Gas) |
| H2 | Hydrogen |

Contact Us
Login
Where to Buy
