PDC Multi-Channel Controller

    Key Features

  • » 
    Up to 8 analog transmitters or up to 128 digital transmitters
  • » 
    RS485 communication with digital transmitters
  • » 
    Relay output modules
  • » 
    Scrolling two line LCD display
  • » 
    LED alarm indicators
  • » 
    Completely field programmable
  • » 
    Low, mid and high alarm setpoints
  • » 
    Audible alarm with silence button
  • » 
    Four wire daisychain wiring
  • » 
    Eight onboard SPDT relays
  • » 
    RoHS compliant circuit boards
  • » 
    Optional BACnet® output module
  • » 
    CSA & UL certified

PDC multi-channel controller is a programmable analog or digital controllers designed to handle a large number of remote transmitters and perform a wide range of control functions. The micro-controller based circuit provides the user with an almost unlimited range of configuration possibilities including simple or complex zoning, changing alarm set points, time delays and relay addressing. The PDC controller can accept inputs from up to 8 analog transmitters or can handle up to 128 digital transmitters on a RS485 communication bus.

Functions that can be set include relay assignment, time delays on make or break, complex zoning, sensor types and ranges, alarm set points and much more. The controller has a two line backlit LCD display that actively scrolls through all programmed channels and displays the gas name, concentration and alarm status. The PDC features LED alarm indicators, audible alarm with silence button, and RoSH compliant circuit boards.

Use with any CETCI analog transmitters, AST or ATW series, or digital transmitters, DST series. Each PDC is pre-programmed at the factory, and is completely field adjustable using a boardmounted push button keypad.

APPLICATIONS

  • » 
    Parking Garages
  • » 
    Repair Shops
  • » 
    Arenas
  • » 
    Pools
  • » 
    Food Processing Plants
  • » 
    and many more

Sensors


Mechanical

PDC Standard Multi-Channel Controllers
Enclosure: Rugged, locakable, powder painted 18 gauge steel
Weight: 4.2 kg (9.2 lb)
Size: 12.3" x 12.3" x 4.2" (311 mm x 311 mm x 106 mm)

 

PDC-W Watertight Multi-Channel Controllers
Enclosure: Watertight Fibreglass
Weight: 4.2 kg (9.2 lb)
Size: 14.0" x 12.0" x 8.0" (356 mm x 305 mm x 203 mm)

Electrical

Power Requirement: 90 - 240 VAC, 47 - 63 Hz
Current Draws: 500 mA (controller only)
Outputs:  4 - 20 mA signals
Relay: 8 dry SPDT contact, 5 amps @ 240 V each
Wiring: Analog: 3 wire shielded
Digital: Daisychain only, shielded
2 wire, 14 gauge stranded power
2 wire, 18 gauge twisted pair network

Input / Output


User Interface


Environmental

Operating Temperature: 0°C to 40°C (32°F to 100°F)
Humidity: 10 - 95% RH non-condensing


Note: Measurements above are sensor dependant.

Certifications

CSA Certification CSA Certified
UL certified UL Certified

Drawings

Product Specification

Sensor Specification

Engineering Specification Samples

DataSheets

Operation Manual

Application Brochure

Quick Application Guide
Quick Application Guide For Fixed Gas Detection SystemsFor Fixed Gas Detection Systems

Miscellaneous Files

PDC Standard Multi-Channel Controllers

Description Code
Up to 8 analog inputs, RS485 digital communication network, LED alarm indicators, LCD digital display, 4 - 20 mA signals, eight 5A @ 240 V SPDT programmable alarm relays, audible alarm w/ silence push-button, 90 - 240 VAC  PDC-A08
Up to 8 digital inputs, RS485 digital communication network, LED alarm indicators, LCD digital display, 4 - 20 mA signals, eight 5A @ 240 V SPDT programmable alarm relays, audible alarm w/ silence push-button, 90 - 240 VAC  PDC-D08
Up to 16 digital inputs, RS485 digital communication network, LED alarm indicators, LCD digital display, 4 - 20 mA signals, eight 5A @ 240 V SPDT programmable alarm relays, audible alarm w/ silence push-button, 90 - 240 VAC  PDC-D16
Up to 24 digital inputs, RS485 digital communication network, LED alarm indicators, LCD digital display, 4 - 20 mA signals, eight 5A @ 240 V SPDT programmable alarm relays, audible alarm w/ silence push-button, 90 - 240 VAC  PDC-D24
Up to 32 digital inputs, RS485 digital communication network, LED alarm indicators, LCD digital display, 4 - 20 mA signals, eight 5A @ 240 V SPDT programmable alarm relays, audible alarm w/ silence push-button, 90 - 240 VAC  PDC-D32
Up to 64 digital inputs, RS485 digital communication network, LED alarm indicators, LCD digital display, 4 - 20 mA signals, eight 5A @ 240 V SPDT programmable alarm relays, audible alarm w/ silence push-button, 90 - 240 VAC  PDC-D64
Up to 96 digital inputs, RS485 digital communication network, LED alarm indicators, LCD digital display, 4 - 20 mA signals, eight 5A @ 240 V SPDT programmable alarm relays, audible alarm w/ silence push-button, 90 - 240 VAC  PDC-D96
Up to 128 digital inputs, RS485 digital communication network, LED alarm indicators, LCD digital display, 4 - 20 mA signals, eight 5A @ 240 V SPDT programmable alarm relays, audible alarm w/ silence push-button, 90 - 240 VAC  PDC-D128

Standard Option

Description Code
Water / dust tight enclosure  W

PDC-W Watertight Multi-Channel Controllers

Description Code
Up to 8 analog inputs, RS485 digital communication network, LED alarm indicators, LCD digital display, 4 - 20 mA signals, eight 5A @ 240 V SPDT programmable alarm relays, audible alarm w/ silence push-button, 90 - 240 VAC, water / dust tight enclosure  PDC-A08-W
Up to 8 digital inputs, RS485 digital communication network, LED alarm indicators, LCD digital display, 4 - 20 mA signals, eight 5A @ 240 V SPDT programmable alarm relays, audible alarm w/ silence push-button, 90 - 240 VAC, water / dust tight enclosure  PDC-D08-W
Up to 16 digital inputs, RS485 digital communication network, LED alarm indicators, LCD digital display, 4 - 20 mA signals, eight 5A @ 240 V SPDT programmable alarm relays, audible alarm w/ silence push-button, 90 - 240 VAC, water / dust tight enclosure  PDC-D16-W
Up to 24 digital inputs, RS485 digital communication network, LED alarm indicators, LCD digital display, 4 - 20 mA signals, eight 5A @ 240 V SPDT programmable alarm relays, audible alarm w/ silence push-button, 90 - 240 VAC, water / dust tight enclosure  PDC-D24-W
Up to 32 digital inputs, RS485 digital communication network, LED alarm indicators, LCD digital display, 4 - 20 mA signals, eight 5A @ 240 V SPDT programmable alarm relays, audible alarm w/ silence push-button, 90 - 240 VAC, water / dust tight enclosure  PDC-D32-W
Up to 64 digital inputs, RS485 digital communication network, LED alarm indicators, LCD digital display, 4 - 20 mA signals, eight 5A @ 240 V SPDT programmable alarm relays, audible alarm w/ silence push-button, 90 - 240 VAC, water / dust tight enclosure  PDC-D64-W
Up to 96 digital inputs, RS485 digital communication network, LED alarm indicators, LCD digital display, 4 - 20 mA signals, eight 5A @ 240 V SPDT programmable alarm relays, audible alarm w/ silence push-button, 90 - 240 VAC, water / dust tight enclosure  PDC-D96-W
Up to 128 digital inputs, RS485 digital communication network, LED alarm indicators, LCD digital display, 4 - 20 mA signals, eight 5A @ 240 V SPDT programmable alarm relays, audible alarm w/ silence push-button, 90 - 240 VAC, water / dust tight enclosure  PDC-D128-W

Calibration Kit

» Complete calibration kits
» All required calibration accessories for field and shop calibration
» Full selection of calibration gases from stock

Remote Strobe Light (for PDC)


Remote Industrial Horn (for PDC)


BACnet Output Module (for PDC)


Remote Relay Module (for PDC)


Remote Power Supply (for PDC)


CAN Network Bridge (for PDC)


Remote Strobe & Horn Combo (for PDC or GEM)

» Rain proof, four strobes
» Hi-impact, polycarbonate enclosure
» Reverse polarity protection

Power Back Up System (for PDC)