LPT is an economical, single sensor, “Low Power Transmitter”. Sensors available include carbon monoxide (CO) and nitrogen dioxide (NO2) which are ideal for vehicle exhaust type applications such as parkades.
LPT transmitter features a two-wire loop, three-wire VDC or four-wire VAC power; making installation a cinch. LPT transmitter also features a 4 - 20 mA linear output signal, automatic thermal resetting fuse, RoHS compliant circuit boards, temperature compensation, and visual LED indication for power and fault conditions and is all enclosed in a standard water / dust tight (drip proof) ABS / polycarbonate enclosure that is equivalent to IP62 (NEMA 12) rating. For splash or hosedown applications, add splash guard.
Includes new sensor CEF (Calibration Extending Firmware) that takes into account the aging of the sensors so that less frequent calibrations are acceptable in non-critical applications.
Automated calibration and other maintenance procedures are simple and easily performed in the field.
APPLICATIONS
»
Parking Garages
»
Repair Shops
»
Ice Cleaning Machine Rooms
»
Manufacturing Plants
»
Maintenance Facilities
Gas Types
Carbon Monoxide (CO)
TCO
Nitrogen Dioxide (NO2)
END
Sensors
Carbon Monoxide (CO) Sensor
Type:
Electrochemical
Range:
0 - 200 ppm
Response Time (T90):
< 150 seconds
Operating Temperature:
-10°C to 60°C (14°F to 140°F)
Operating Humidity:
5 - 95% RH non-condensing
Operating Pressure:
N/A
Repeatability:
< 2% of signal
Maximum Zero Shift:
N/A
Clean Air Output Drift:
< 10 ppm equivalent per year
Expected Life Span:
6 - 7 years in air (under normal conditions)
Calibration:
Every 6 months or once a year (depending on application)
Linear 4 - 20 mA
Maximum 216 Ω load (wiring plus termination resistor) at 16 VDC
Maximum 316 Ω load (wiring plus termination resistor) at 12 VAC
Wiring:
VDC two or three conductor shielded 18 awg stranded
VAC four conductor shielded 18 awg stranded
Fuse:
Automatic resetting thermal
Indicator:
Solid Green: Power ON
Flashing Green (50% duty cycle): Warm up
Flashing Green (short OFF, long ON): Fault mode
LED OFF: No Power or 4-20 mA “Open Loop” (unit won’t operate)
» 16 gauge, clear anodized metal protective guard » Larger size for controllers & self-contained systems » Smaller size for analog & digital transmitters
» Full selection of calibration gases from stock » All required calibration accessories for field and shop calibration » Full service and calibration shop for fixed gas detection instruments